Royce now offers a complete line of Interface
Level Analyzers that make it possible to reliably monitor
and control the solid/liquid interfaces in settling tanks
and clarifiers; regardless of the size of the plant, process
or budgetary constraints.
The Royce series of Interface Level Analyzers use an ultrasonic
ranging technique to measure the depth of interfaces within
the tank. The 25 dual series sensor is available in polyurethane
for standard applications and Kynar for high temperature or
chemical applications. The sensor is mounted just below the
surface of the water. Royce offers a hinged bracket sensor
mounting option that accommodates surface skimmer passage
automatically with the rotation of the rake.
The Model 2501A is a low-priced instrument designed
for interface monitoring applications which do not require
control outputs.
The Model 2511A is capable of having
the ultrasonic speed-of-sound signal from its transducers
changed by the user in applications where liquid mediums other
than water are in use; it also has four setpoint relays which
can each be used as either a high or low
setpoint. The Model 2511A also has a serial output available
for the purpose of tying a number of the units to a central
process control computer. The Model 2505 system incorporates
all the features of the 2511A allowing individual monitoring
and control on every primary, secondary, and thickening clarifier
in the planteconomically.
Features:
- No moving parts, no maintenance, no recalibration required.
- Surface skimmer friendly.
- Microprocessor based electronics.
- Back-lit LCD displays.
- Full featured set point relays available (Models 2511A/2505).
- Simple, user friendly menu driven programming.
- Numerical and graphical displays.